7. MODBUS
IMS01J02-E2
128
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Heat-side proportional
band
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W
C
0.1 to 1000.0 % of span
H-TIO- ,
H-CIO-A:
3.0
H-SIO-A:
300.0
Cool-side proportional
band
[H-TIO- , H-CIO-A]
R/W
C
0.1 to 1000.0 % of span
3.0
Integral time
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W
C
1 to 3600 seconds
H-TIO- ,
H-CIO-A:
240
H-SIO-A:
2
Derivative time
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W
C
0 to 3600 seconds (0: PI action)
H-TIO- ,
H-CIO-A:
60
H-SIO-A:
0
Overlap/deadband
[H-TIO- , H-CIO-A]
R/W C
−
10.0 to
+
10.0 % of span
0.0
Control response
parameters
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W
C
0: Slow 1: Medium 2: Fast
In order to perform PID control by using the
fuzzy function, specify “Fast.” The fuzzy
function is effective to restrict overshoot or
undershoot occurring at operation start, or
resulting from set value changes.
(Fuzzy function correspond to H-TIO-P/R
module only.)
0 *
* Heat control (H-TIO- /H-CIO-A): 0
Heat/cool control (H-TIO- /H-CIO-A): 2
Position proportioning control (H-TIO-K): 0
Speed control (H-SIO-A): 0
Continued on the next page.