![RKC INSTRUMENT SR Mini HG SYSTEM H-PCP-J Скачать руководство пользователя страница 152](http://html.mh-extra.com/html/rkc-instrument/sr-mini-hg-system-h-pcp-j/sr-mini-hg-system-h-pcp-j_instruction-manual_1466668152.webp)
7. MODBUS
IMS01J02-E2
144
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
H-DO-G manipulated
output value
[H-DO-G]
RO C
−
5.0 to
+
105.0 %
−
H-DO-G output limiter
(high)
[H-DO-G]
R/W
C
Output limiter (low) to 105.0 %
100.0
H-DO-G output limiter
(low)
[H-DO-G]
R/W C
−
5.0 % to Output limiter (high)
0.0
H-DO-G output cycle
time
[H-DO-G]
R/W
C
1 to 100 seconds
2
H-DO-G master channel
setting
[H-DO-G]
R/W
C
0 to The number of H-TIO- module use
channel (0: Unused)
0
H-DO-G output ratio set
value
[H-DO-G]
R/W
C
0.001 to 9.999
1.00
H-DO-G Auto/Manual
transfer
[H-DO-G]
R/W
C
0: Auto 1: Manual
Setting will be invalid in ON/OFF control
and heat/cool control.
0
H-DO-G manual output
value
[H-DO-G]
R/W C
−
5.0 to
+
105.0 %
Setting will be invalid in ON/OFF control
and heat/cool control.
0.0
Continued on the next page.