7. MODBUS
IMS01J02-E2
133
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Output limiter (low)
[For heat/cool control:
Cool-side output limiter
(high)]
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W C [Heat control, Position proportioning control
and Speed control]
−
5.0 % to Output limiter (high)
[Heat/cool control]
Cool-side output limiter (high):
−
5.0 % to
+
105.0 %
Cool-side output limiter (low):
−
5.0 % (fixed)
0.0
a
Output change rate
limiter (up)
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W
C
0.0 to 100.0 %/second (0.0: OFF)
Setting will be invalid in ON/OFF control.
0.0
Output change rate
limiter (down)
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W
C
0.0 to 100.0 %/second (0.0: OFF)
Setting will be invalid in ON/OFF control.
0.0
Display scale high
[H-TIO-H/J, H-CIO-A,
H-SIO-A]
R/W
C
Span 10000 or less
b
(Within
−
9999 to
+
10000)
H-TIO-H/J,
H-CIO-A:
100.0
H-SIO-A:
300
Display scale low
[H-TIO-H/J, H-CIO-A,
H-SIO-A]
R/W
C
Span 10000 or less
b
(Within
−
9999 to
+
10000)
H-TIO-H/J,
H-CIO-A:
0.0
H-SIO-A:
0
Digital filter
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W C H-TIO-A/B/C/D/K/P
0 to 100 seconds (0: OFF)
H-TIO-E/F/G/H/J/R, H-CIO-A, H-SIO-A
0.0 to 100.0 seconds (0.0: OFF)
0 or 0.0
a
Heat control (H-TIO- /H-CIO-A): 0.0
Heat/cool control (H-TIO- /H-CIO-A): 100.0
Position proportioning control (H-TIO-K): 0.0
Speed control (H-SIO-A): 0
b
The position of the decimal point differs depending on Decimal point position (P. 135) setting.
Continued on the next page.