7. MODBUS
IMS01J02-E2
140
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Number of alarm delay
times
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U 0 to 255 times
0
DO function selection
[H-DO-A/B/D]
R/W M 00 to 88 *
The factory
set value
varies
depending
on the
specifications
when
ordering.
DI function selection
[H-DI-A]
R/W M 0: Unused
1: Function mode 1
−
Memory area transfer (ENABLE terminal
is used)
After area selection setting, the actual
area is changed by detecting the
ENABLE edge.
−
Control RUN/STOP transfer
−
Alarm interlock release
2: Function mode 2
−
Memory area transfer
The actual area is changed approximately
2 seconds after area selection setting.
−
Control RUN/STOP transfer
−
Alarm interlock release
1
* DO function selection (H-DO-A/B/D module)
0 0
0 0
Continued on the next page.
Data range
0: No alarm function
1: Alarm 1
2: Alarm 2
3: Burnout
4: Heater break alarm (HBA)
5: AI alarm 1
6: AI alarm 2
7: Control loop break alarm (LBA)
8: (Not settable)
Block 2 (DO5 to DO8)
Block 1 (DO1 to DO4)
Setting will be valid for only block 1
(DO1 to DO4) in case of H-DO-B module.
H-DO-A/B module
Block 2 (DO9 to DO16)
Block 1 (DO1 to DO8)
H-DO-D module