2. SPECIFICATIONS
IIMS01J02-E2
17
Synchronous method:
Start/stop synchronous type
Communication speed:
9600 bps, 19200 bps, 38400 bps
Communication speed can be selected with switch
Data bit configuration:
Start
bit:
1
Data bit: 7 or 8
Parity bit: Without, Odd or Even
Without for 8 data bits
Stop bit: 1 or 2
Data bit configuration can be selected with switch
Connected equipment:
Host computer, touch panel, operation panel or PLC
Signal logic:
RS-422A/RS-485
Signal voltage
Logic
V (A)
−
V (B)
≥
2 V
0 (SPACE)
V (A)
−
V (B)
≤
−
2 V
1 (MARK)
Voltage between V (A) and V (B) is the voltage of (A) terminal for the
(B) terminal.