7. MODBUS
IMS01J02-E2
141
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
DI using selection
[H-DI-A]
R/W
M
0 to 255 *
255
H-PCP-J module
DO type selection
[H-PCP-J]
R/W
C
0: No alarm function
1: Alarm 1/TI alarm 1
2: Alarm 2/TI alarm 2
3: Burnout
4: Heater break alarm (HBA)
5: Temperature rise completion output
6: AI alarm 1
7: AI alarm 2
8: Control loop break alarm (LBA)
9: FAIL output
10: PLC communication status
[Action]
1 to 4, 6 to 8:
Closed at alarm occurrence
5: Closed at temperature rise completion
9: Open at fail occurrence
10: Closed at communication with PLC
Be action of energized case. Action
reverses in case of de-energized.
(For the energize/de-energized, see
H-PCP-J module DO de-energized
selection.)
CH1: 9
CH2: 1
CH3: 2
CH4: 3
CH5: 4
CH6: 5
CH7: 8
CH8: 10
* DI using selection (H-DI-A module)
×
: Used
−
: Unused
Setting
data
Memory area
transfer
Control RUN/STOP
transfer
Alarm interlock release
63
127
191
255
×
×
×
48
−
×
×
47
×
−
×
32
−
−
×
31
×
×
−
16
−
×
−
15
×
−
−
0
−
−
−
Continued on the next page.