6. RKC COMMUNICATION
IMS01J02-E2
88
Continued from the previous page.
Name
Iden-
tifier
Digits Attri-
bute
Struc-
ture
Data range
Factory
set
value
Alarm 1 action at input
error
[H-TIO- , H-CIO-A,
H-SIO-A]
OA
1 R/W
U 0: Normal alarm action
1: Forced alarm ON when
temperature measured
value exceeds abnormal
input trigger input.
0
Alarm 2 action at input
error
[H-TIO- , H-CIO-A,
H-SIO-A]
OB
1 R/W
U 0: Normal alarm action
1: Forced alarm ON when
temperature measured
value exceeds abnormal
input trigger input.
0
Number of alarm delay
times
[H-TIO- , H-CIO-A,
H-SIO-A]
DF
6
R/W
U
0 to 255 times
0
Module initialization *
[H-PCP-J]
CL
1 R/W
U 0: Normal state (Initialization
is not executed)
1: Initialize only the new
module (Only modules
which are not recognized
by the H-PCP-J module
are initialized)
2: Initialize all module
Only 1 or 2 can be used in
the selecting and the value
will automatically return to 0
after the selection of 1 or 2.
0
* Initialize method for changing the module composition
To change module configuration, use the following procedures:
•
When a module is added to the control unit...................................Initialize only the new module
•
When a module is deleted from the control unit ............................Initialize only the new module
•
When a module is inserted (added) between the modules
in the control unit ...........................................................................Initialize all modules
•
To change the arrangement of the modules in the control unit ......Initialize all modules
Note that when all modules are initialized all internal data of all modules are set to the
default values.
Continued on the next page.