![RKC INSTRUMENT SR Mini HG SYSTEM H-PCP-J Скачать руководство пользователя страница 161](http://html.mh-extra.com/html/rkc-instrument/sr-mini-hg-system-h-pcp-j/sr-mini-hg-system-h-pcp-j_instruction-manual_1466668161.webp)
7. MODBUS
IMS01J02-E2
153
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Event DO status
[H-DO-C]
RO M
Event DO manual output
value
[H-DO-C]
R/W M
The respective channel status is assigned to
each bit in the holding register.
bit 0: CH1 (DO 1)
bit 1: CH2 (DO 2)
bit 2: CH3 (DO 3)
bit 3: CH4 (DO 4)
bit 4: CH5 (DO 5)
bit 5: CH6 (DO 6)
bit 6: CH7 (DO 7)
bit 7: CH8 (DO 8)
bit 8 to 15: Unused
Bit data 0: OFF 1: ON
[Decimal number: 0 to 255]
0
Event DO extension
alarm set value
[H-DO-C]
R/W C TC/RTD input:
Within input range or span range
Current/voltage input, H-SIO-A:
Within display scale range or span range
0
a
Event DO function
selection
[H-DO-C]
R/W
C
0 to 30
b
0
Event DO corresponding
channel setting
[H-DO-C]
R/W
C
1 to 40
b
1
Event DO mode select
setting
[H-DO-C]
R/W
C
0 to 40
b
0
Event DO extension
alarm differential gap
[H-DO-C]
R/W
U
0.00 to 10.00 %
0.10
Event DO extension
alarm interlock
[H-DO-C]
R/W
U
0: Not provided
1: Provided
0
Number of Event DO
extension alarm delay
times
[H-DO-C]
R/W
U
0 to 255 times
0
a
The position of the decimal point differs depending on the input range.
b
Set the function, corresponding channel and mode select of Event DO. Event DO uses it with event
output function.
For the data, see the
Event output function (P. 101)
.