Engineer Programming
Page
65
Quick Keys
Parameter
Default
Range
Inactivity Timer
0
0-255 minutes
This timer relates to Automatic Set/Unset scheduler. If there is no signal
from any of the zones located in a partition that is defined under an
Set/Unset scheduler for the time defined as
Inactive Timer
then the
automatic schedule will be activated and the relevant partitions will be
auto set (according to the schedule definition).
Note: The Inactive Timer of the scheduling program should be defined as
ON under User Menu> Clock>Scheduler>Weekly>Schedule
#>Set/Unset>6) Inactive.
Controls
The System Control menu contains parameters that control specific system operations.
Access and configure the parameters in the system control menu, as follows:
System: Controls: Basic
Quick Keys
Parameter
Default
Range
Basic Programming
This section refers to the most common controls in the system.
Quick Set
Yes
Yes/No
YES
: Eliminates the need for a user code when arming (Full or partial).
NO
: A valid user code is required for arming (Full or partial).
Quick PO
Yes
Yes/No
YES
: A user can activate a programmable output without the need to
enter a user code.
NO
: A user code is required to activate a programmable output.
Allow Omit
Yes
Yes/No
YES
: Permits zone omitting by authorized system users after entering a
valid user code.
NO
: Zone omitting is NOT permitted.
Quick Omit
No
Yes/No
YES
: Eliminates the need for a valid user code when omitting zones.
NO
: Qualified users must enter a valid user code to omit zones.