RD 500 RD51
Converter Technical Data
3-7
DOK-RD500*RD51*******-IB04-EN-P
3.7
Technical Data for Size Classes C, D and E with Pulse
Frequency f
p
= 12 kHz
12 kHz
RD51.1
022
030
037
045
055
075
090
110
Supply voltage, 3-phase 380 ... 480 V AC (±10 %)
1)
Output frequency Hz
0 - 1400
Rated current
A
30
35
40
52
68
80
80
80
Peak current for t = 60 s A 39
46
52
68
88
104
104
104
t = 1 s A 51
60
68
88
116
136
136
136
t = 0.5 s A 60
70
80
104
136
160
160
160
Rated output S
N
kVA
20
23
26
34
45
53
53
53
Peak power for t = 60 s kVA
26
30
34
44
58
68
68
68
Ambient conditions, noise suppression level, interference immunity
Environmental class
3K3 according to DIN IEC 721-3-3 (ambient temperature 0 – 40 °C operation, to
50 °C power reduction at 2.5 % per K)
Cooling air requirement m³ / s
0.1
0.1
0.2
0.2
0.4
0.4
0.4
0.4
Power loss kW 0.9
1.0
1.1
1.4
1.9
2.2
3.2
3.5
Radio int. sup. level/noise immunity
A 1 according to EN 55011 / EN 61800-3
Mechanical design
Size classes
C
C
C
C
D
D
E
E
Degree of protection
IP 20 according to EN 60529 (without connection terminals)
Weight of converter for the various cooling types
L Forced air cooling kg 36
36
36
36
52
52
74
74
W Liquid cooling kg 28
28
28
28
42
42
57
57
D Plug-through cooler kg
33
33
33
33
49
49
71
71
Performance data of chopper
Continuous power
kW
14
19
23
27
33
45
55
55
Peak power for t = 1 s kW
56
74
93
111
130
148
260
260
Minimum resistance value
Ω
11.7
8.8
7
5.8
5
4.4
2.5
2.5
1:
Starting at an output voltage Ua >400 V, the rated current is linearly
reduced from 100 % to 83 % for Va = 480 V.
Содержание RD 500 Series
Страница 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 275: ......