Electrical Installation of Converter
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
Parameterizing the Converter
The configuration of the standard RS485 interface should be set using
parameters P0500 to P0506.
The parameters are accessed as follows via the menu:
PARAMETERIZATION/PROMPTEDPARAMETR/SER.
COMMUNICATION
Parameterizing the Standard RS485 Interface
Parameter
No.:
Name
Description / explanation
of selectable options
Factory setting
min / max values
Pass-
word
0500
SS1 protocol X12
Serial interface 1 (SS1) is a RS485
interface (X12 connection)
Parameter value:
0 = no protocol
1 = USS 4 / 2 words
2 = USS 4 / 6 words
3 = USS 0 / 2 words
4 = USS 0 / 6 words
5 = USS 4 / 0 words
USS 4 / 6 words
0 - 5
2
0501
SS1 baud rate X12
Parameter value:
0 = no protocol
1 = 1200 Baud
2 = 4800 Baud
3 = 9600 Baud
4 = 19,200 Baud
5 = 38,400 Baud
6 = 76,800 Baud
9600 baud
0 - 6
2
0502
SS1 parity X12
Parameter value:
0 = no parity
1 = ODD
2 = EVEN
EVEN
0 - 2
2
0503
SS1 stop bits X12
Either 1 or 2 stop bits can be set.
1
1 - 2
2
0504
SS1 slave address
For the RS485 bus, the address of the
device can be set between 0 and 31.
Caution: This address must be unique
on the bus, i.e. there must be no
identical addresses!
0
0 - 31
2
0505
SS1 Rx monitoring
Parameter value:
0 = no action
1 = warning
2 = malfunction
Fault
0 - 2
2
0506
SS1 Rx mon. time
Monitoring time for standard interface
SS1.
If the interface does not receive an
error-free protocol within this time, the
response selected in P0505 is initiated.
0.1 s
0.1 - 60.0 s
2
Fig. :4-23
Parameters for RS485
Содержание RD 500 Series
Страница 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 275: ......