8-22
Parameter Value Assignment
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
Additional functions
Para-
meter
No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass-
word
0282.00
Rounding ramp up
0.000 s
1
Rounding-off times UP for the ramp-function
generator.
This is used for jerk limiting when starting; this is
generally not more than 1 / 10 of the ramp time.
0.000 ... 800.00 s
0283.00
Rounding ramp
down
0.000 s
1
Diagram, ramp-up / ramp-down ramp with rounding-
off
0.000 ... 800.00 s
0249
RFG up/down mode
Ramp-up and ramp-down with direction of
rotation reversal
1
2
Ramp-up and ramp-down with direction of rotation
reversal
0 = sign
1 = value
0 / 1
DG510005EN00.FH9
t
100 %
0 %
Ramp-up time
(P0280)
Setpoint
Rounding-off DOWN 1
(P0283)
Rounding-off UP 1
(P0282)
Setpoint
RFG output
t
Acceleration
0
Phase 1
Phase 2
Phase 3
1
2
3
Ramp-down time
(P0280)
Fig. 8-8: Up and down ramp with rounding-off