Parameter Value Assignment
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
Para-
meter
No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass-
word
0546
DC braking current
Supplementary parameter for “braking
operation” from P0043 and P0044:
5.00 %
1
100 % corresponds to the contents of parameter
P0374 (factory setting: Continuous output current of
the drive).
1.00 ... 100.00 %
1
0545
DC braking time
Supplementary parameter for “braking
operation” from P0043 and P0044:
0.0 sec
1
0.0 ... 100.0 sec
0045
Timeout for f-null
Supplementary parameter for “braking
operation” from P0043 and P0044:
1.5 sec
2
0.0 ... 300.0 sec
0087
Searching mode
no
2
0 = no:
The drive starts as normal after an on command
without a search run.
1 = after on:
After the on command, the drive starts with the last
direction of rotation and searches for the motor
which is coasting down from f max towards 0 Hz. If
the motor frequency is found, or for f = 0 Hz, the
actual setpoint is approached via the ramp-function
generator.
2 = after on ±:
After the on command, the drive starts with the last
direction of rotation and searches for the motor
which is coasting down from f max towards 0 Hz. If
the motor is not found by f = 0 Hz, then a search is
made from f max towards 0 Hz with the other
direction of rotation. If the motor frequency is found,
or for f = 0 Hz, the actual setpoint is approached via
the ramp-function generator.
0 ... 2
0088
Restart
no
2
Restart after power failure:
0 = no: The drive only starts after the line supply
voltage returns if the drive detects a rising edge of
the on command.
1 = yes: The drive automatically starts if, when the
line supply voltage returns, the drive as an on
command.
0 / 1
Thermal motor protection
Para-
meter
No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass-
word
0385
Select KTY / PTC
X15
PTC
2
Selects the thermistor protection.
0 = without , 1 = KTY , 2 = PTC
0 ... 2
0386
KTY alarm X15
Supplementary parameter for KTY in P0385
135 °C
1
Enters the motor temperature to initiate the alarm.
30 ... 180 °C
0387
KTY fault X15
Supplementary parameter for KTY in P0385
155 °C
1
Enters the motor temperature to initiate the fault.
30 ... 195 °C
Содержание RD 500 Series
Страница 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 275: ......