4-20
Electrical Installation of Converter
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
X80, Starting lock-out
RD51.1-x-
Type
pole number
Execution
022
plug-in connection
4
Plug on device
030
plug-in connection
4
Plug on device
037
plug-in connection
4
Plug on device
045
plug-in connection
4
Plug on device
055
plug-in connection
4
Plug on device
075
plug-in connection
4
Plug on device
090
plug-in connection
4
Plug on device
110
plug-in connection
4
Plug on device
Tab. 4-41
Execution
Identification single connection
Identification signification
1
2
During operation, terminals 1 - 2 must be closed; when they are
opened, the start of the connected motor is inhibited.
3
4
Starting lock-out floating acknowledge contact,
30 V DC / 1 A N / C contact
Tab. 4-42
Identification single connection
RD51.1-x- Recommended
minimum cross-section
mm²
AWG
Cable cross-
section which can be
connected, mm²
AWG
022
1
18
0.08 – 1.5
28 - 16
030
1
18
0.08 – 1.5
28 - 16
037
1
18
0.08 – 1.5
28 - 16
045
1
18
0.08 – 1.5
28 - 16
055
1
18
0.08 – 1.5
28 - 16
075
090
1
18
0.08 – 1.5
28 - 16
110
1
18
0.08 – 1.5
28 - 16
Tab. 4-43
Connection cross-section
0,22 – 0,25 Nm
Execution
Connection cross-section
Torque
Содержание RD 500 Series
Страница 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 275: ......