![REXROTH RD 500 Series Скачать руководство пользователя страница 191](http://html1.mh-extra.com/html/rexroth/rd-500-series/rd-500-series_applications-manual_1449588191.webp)
RD 500 RD51
Electrical Installation of Inverter
6-17
DOK-RD500*RD51*******-IB04-EN-P
X2, cable damping L1
RD51.1-xx-
RD51.3-xx-
Type
Number
Execution
022
High current bushing terminal
2
Screw connection
030
High current bushing terminal
2
Screw connection
037
High current bushing terminal
2
Screw connection
045
High current bushing terminal
2
Screw connection
055
High current bushing terminal
2
Screw connection
075
High current bushing terminal
2
Screw connection
090
High current bushing terminal
2
Screw connection
110
High current bushing terminal
2
Screw connection
Tab. 6-34
Execution
Identification single connection
Identification signification
C3
DC link L+
D3
DC link L-
Tab. 6-35
Identification single connection
RD51.1-xx-
RD51.3-xx-
Cable cross-
section which can be connected 1),
mm²
AWG
Torque
in Nm
022
0.5 – 10
20 – 8
1.5 – 1.8
030
0.5 – 10
20 – 8
1.5 – 1.8
037
0.5 – 10
20 – 8
1.5 – 1.8
045
0.5 – 10
20 – 8
1.5 – 1.8
055
0.5 – 16
20 – 6
2.0 – 2.3
075
0.5 – 16
20 – 6
2.0 – 2.3
090
0.5 – 16
20 – 6
2.0 – 2.3
110
0.5 – 16
20 – 6
2.0 – 2.3
1):
As a result of the terminal size
Tab. 6-36
Connection cross-section
See table.
Note:
The additional function L1 is required to connect the motor
filter RZM01.1-108 or RZM01.1-130 in inverter of power class
075 and 090.
Execution
Connection cross-section
Torque
Содержание RD 500 Series
Страница 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 275: ......