5-18
Inverter Technical Data
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
DG0006F1.FH7
Ambient temperature in °C
0,7
1
40
45
50
55
5
Degree of utilization at higher
ambient temperatures
Load f
actor
Fig. 5-6:
Utilization at a higher ambient temperature
Setup Elevations Exceeding 1000 Meters above Sea Level:
The utilization of the inverter must be reduced (derated) corresponding to
the diagram below for installation altitudes above 1000 meters above sea
level.
83%
80%
90%
100%
500
70%
0
1000
1500
2000
2500
Utilization
Insallation altitude in m above sea level
DGZU0008EN00.FH9
Fig.: 5-7 Derating depending on setup elevation
5.14 Mounting Inverter Size Classes A to E
•
The RD 500 units, sizes A to E are modular and are designed for
mounting in cabinets.
•
The units have a 22.5 mm mechanical grid pattern. Several drive
units can be mounted next to one another without any intermediate
space (with the exception of device size classes A - B with cooling
type P) when using mounting rails with tapped holes (also refer to the
assembly example).
•
Assembly must be carried out perpendicular to a level construction
area.
•
A minimum clearance of 100 mm above and below the unit must be
maintained to ensure that the cooling air can flow unrestricted.
Содержание RD 500 Series
Страница 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 275: ......