8-8
Parameter Value Assignment
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
Para-
meter
No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass-
word
0196
Mot. pot. mode
Supplementary parameter for “motor
potentiometer”.
Start f set, expon.
1
For Start f set, the motor potentiometer setpoint,
which was set the last after the off command, is
approached.
For Start f min, the actual f min (P0180.XX) is
approached.
Furthermore, the rate-of-change of the motor
potentiometer can be set using the parameter:
linear = Uniform change corresponding to the
selected step width
expon. = The rate-of-change increases the longer
that the button remains pressed
0 = Start f set, linear
1 = Start f min, linear
2 = Start f set, exponential
3 = Start f min, exponential
0 ... 3
1
0195
Mot. pot. step value
Supplementary parameter for “motor
potentiometer”.
0.01
1
The motor potentiometer rate-of-change is set using
the step width.
0.01 ... 10.00 Hz
0265.XX Fix value main s / p
Supplementary parameter for “fixed setpoint”.
5.00 %
1
Parameter P0390 is the reference value for the
frequency setpoints and actual values.
P0390 is set to 50 Hz in the factory. This means that
to operate the motor with 50 Hz, a setpoint of 100 %
must be entered.
XX = The index, in which a value can be saved, is
selected in parameters P0875, P0876; P0877;
P0878, P0879 or P0880 (function: Setpoint memory,
bits 20 ... 23).
-199.99 ...
199.99 %
1
0200.00
Analog input norm.
Supplementary parameter for “analog input”.
100 %
2
The analog input normalization refers to the
frequency normalization P0390.
-199.99 ...
199.99 %
2
0202.00
Analog input offs.
Supplementary parameter for “analog input”.
0.00 %
2
Analog input offset
-199.99 ...
199.99 %
0203.00
Analog input sign.
Supplementary parameter for “analog input”.
Direct
2
Analog input signal
0 = direct
1 = absolute value
2 = inverted
3 = absolute value, inverted
0 ... 3
0204.00
Analog input filtr.
Supplementary parameter for “analog input”.
2 ms
2
Analog input, filter time to smooth the analog signal.
0 ... 10000 ms
Содержание RD 500 Series
Страница 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Страница 275: ......