Table 1. Operator Troubleshooting – Mechanical (Cont).
ITEM
CONDITION/INDICATION
POSSIBLE MALFUNCTION
CORRECTIVE ACTION
Poor or improper fuel supply
Check fuel type and quality.
Drain and clean fuel tank and system
if necessary.
Low Fuel Pump pressure.
Check fuel pump pressure, adjust to
proper specifications.
Remove and replace fuel pump if
necessary.
Contact REEVES EMS.
Dirty fuel nozzle.
Remove and replace fuel nozzle if
necessary.
Improper air adjustment
setting.
Adjust accordingly to the procedures
listed in Maintenance every 3 months.
Scale buildup in heat
exchanger coil.
Contact REEVES EMC for de-scaling
procedures.
5.
Burner runs, but will not
heat.
Low Fuel Pump pressure.
Check fuel pump pressure, adjust to
proper specifications.
Remove and replace fuel pump if
necessary.
Contact REEVES EMS.
Low fuel.
Refill with fuel.
Cold combustion chamber.
Run burner for several minutes. If
condition does not improve proceed
with next step.
Dirty fuel nozzle.
Remove and replace fuel nozzle.
6.
Burner discharges white
smoke.
Improper air adjustment
setting.
Adjust accordingly to the procedures
listed in Maintenance every 3 months.
Содержание G2 series
Страница 2: ......
Страница 12: ......
Страница 22: ......
Страница 34: ......
Страница 36: ......
Страница 42: ......
Страница 44: ......
Страница 56: ......
Страница 58: ......
Страница 60: ......
Страница 66: ......
Страница 112: ......
Страница 116: ......
Страница 118: ......
Страница 152: ......
Страница 180: ......
Страница 183: ......