9
Start up
1.
Connect the device hydraulically to the
installation.
2.
Connect the device to the supply
voltage.
3.
If necessary set:
n
the language - see
Ä
Chapter 8.4.6
„"Language" main
menu“ on page 41
n
the measured variable to "mass"
and density of the feed chemical -
see
Ä
on page 25
n
the units - see
Ä
Chapter 8.4.2.1
„"Display" menu“ on page 26
n
the current output - see
Ä
Chapter
8.4.2.3 „"Current output"
menu“ on page 28
n
the counter output - see
Ä
Chapter
8.4.2.2 „"Counter output"
menu“ on page 26
4.
Allow the metering pump to prime -
press both
[arrow keys]
simultaneously
at the pump control unit.
5.
At the device acknowledge the error
„bubbles“
by pressing the key
[P]
.
6.
Allow the metering pump to run.
7.
Check whether the displayed values are
plausible.
8.
Check whether the stroke feedback to
the metering pump is plausible.
9.
Check whether the frequency signals
and the mA signals of the device have
the expected effect if these signals are
being used.
If the metering pump goes into fault mode
during start up, press the [P] key to
acknowledge.
Use with the metering pump delta
®
is only
possible if the pump is set to "dosing" -
"set-up" (discharge stroke)" - "fast".
Operation as a flow meter
1.
In the menu
„calibration“
calibrate the
„quantity“
- see
Ä
Chapter 8.4.3.2 „Cali‐
brate "quantity"“ on page 35
2.
Check whether the displayed values are
plausible.
Operation as a dosing monitor
1.
Under
„set-up
è
set counter output“
to
„stroke feedback“
.
2.
Connect the device cable with the
"dosing monitor" terminal of the pump.
3.
In the menu
„calibration“
set the
„stroke
feedback“
- see
Ä
Chapter 8.4.3.1 „Cali‐
brate "stroke feedback"“ on page 29
Function "transmit error signal"
(for identity code characteristic "signal output"
"1")
1.
Under
„set-up
è
current output
è
error current“
set the desired error
result and set the
„error current“
.
2.
Cause the error to occur and check
whether everything functions as desired.
Start up