Chapter 3 Environment description and installation
3-8
E.
Fuse types
Drive input fuses are provided to disconnect the drive from power in the event that a component fails in the drive’s
power circuitry. The drive’s electronic protection circuitry is designed to clear drive output short circuits and ground
faults without blowing the drive input fuses. Below table shows the EV input fuse ratings.
To protect the inverter most effectively, use fuses with current-limit function.
RK5, CC/T type fuse for EV
110V class(1
φ
)
JNEV- HP
KW
KVA
100% CONT
Output AMPS (A)
Max.RK5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
1P2-H1
0.25 0.2 0.53
1.7
10 20
1P5-H1
0.5 0.4 0.88
3.1
15 30
101-H1
1 0.75 1.6
4.2
20 40
220V class(1
φ
)
JNEV- HP
KW
KVA
100% CONT
Output AMPS (A)
Max.RK5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
2P2-H1 0.25
0.2
0.53
1.7
8
15
2P5-H1 0.5
0.4
0.88
3.1
10
20
201-H1 1
0.75
1.6
4.2
15
30
202-H1 2
1.5
2.9
7.5
20
40
203-H1 3
2.2
4.0
10.5
25
50
220V class(3
φ
)
JNEV- HP
KW
KVA
100% CONT
Output AMPS (A)
Max.RK5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
2P2-H3 0.25
0.2
0.53
1.7
5
8
2P5-H3 0.5
0.4
0.88
3.1
8
10
201-H3 1
0.75
1.6
4.2
12
15
202-H3 2
1.5
2.9
7.5
15
20
203-H3 3
2.2
4.0
10.5
20
30
440V class(3
φ
)
JNEV- HP
KW
KVA
100% CONT
Output AMPS (A)
Max.RK5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
401-H3 1
0.75
1.7
2.3
6
10
402-H3 2
1.5
2.9
3.8
10
15
403-H3 3
2.2
4.0
5.2
10
20
*
Fuse ratings are based upon 300V fuses for 120V inverters, and 300V fuses for 230V inverters, and 500V for
460V inverters