Chapter 3 Environment description and installation
3-25
z
EV-202/203/401/402/403—N4X(IP65)TYPE INSTALLATION:
T1 T2 T3
3 Phases
IM
220-240V
380-480V
Single/ThreePhases
DATA
FUN
DSP
ENT
RUN
RESET
STOP
REV-0-FWD
SWITCH
Potentiometer
POWER
SWITCH
L1(L) L2(N) L3
2.Power supply cable : 4.
Torque value of Screw :
EV-200 #12AWG(3.5mm²) (1).Power/Motor cable(TM1,
EV-400 #16AWG(1.25mm²) TM3)
3.
Motor cable : Terminal : 8 kgf-cm(6.94 in-lb)
EV-200 #14AWG(2.0mm²) (2).Remote control wire :
EV-400 #16AWG(1.25mm²) 4 kgf-cm(3.47 in-lb)
(3).Outer Cover (M4) :
8kgf-cm(6.94 in-lb)
NOTE:
1.POWER SWITCH,REV-0-FWD SWITCH
AND Potentiometer are only for EV-202~403-
N4S TYPE
CIRCUIT DIAGRAM
NOTE:
(1).Input source: single-phase (L1(L),
L3
(N),
) ensuring
that it is connected to a 200/240 supply or three-plase
(L1 (L),
L2, L3(N)
,
) ensuring that it is connected
to a 200/240,380/480V supply.
(2).Output Motor: three-phase (
, T1, T2, T3).
Caution:
.
Do not start or stop the inverter using the main
circuit power.
.
FOR EV-202~403--N4S TYPE:
Please always remain REV-0-FWD switch at 0
position. In order to keep inverter has no running
signal before power-on again after power supply
interrupted. Otherwise, injury may result.
.
FOR EV-202~403--N4 TYPE:
Please always remain RE or FW switch at OFF
position. In order to keep inverter has no running
signal before power-on again after power supply
interrupted. Otherwise, injury may result.
L2
L3(N
)
(N
)