Chapter 3 Environment description and installation
3-16
Over load protection Inverter rated current 150%/1min
International
conformity
UL/CE
Over voltage
230V Class: DC voltage >
410
V 460V Class: DC voltage >
820
V
Under voltage
230V Class: DC voltage <190V 460V Class: DC voltage <380V
Instantaneous power
loss restart
Set to enable or disable
Stall prevention
ACC/DEC/ Operation stall prevention and stall prevention level.
Output terminal
short circuit
Electronic circuit protection
Other faults
Electronic circuit protection
Protective F
unctions
Other functions
Over current, over voltage, under voltage, over load, instantaneous power loss
restart, ACC/DEC/ Operation stall prevention, output terminal sort circuit,
grounding error, reverse limit, directly start as power on and fault reset limit.
※
Note: The setting resolution of above 100 Hz is 1Hz when controlled by keypad, and 0.01
Hz when controlled using computer (PC) or programmable controller (PLC).