Chapter 4 Software index
4-33
C46 (Option card) Multi-function output T+, T-
000: Run
001: Frequency reached [Preset target frequency ± F23]
002: Frequency reached [ Preset output frequency level (F22) ±F23]
003: Frequency detection (>F22)
004: Frequency detection (<F22)
005: Fault.
006: Auto-restart
007: Momentary power loss
008: Emergency Stop (E.S.)
009: Base Block (b.b.)
010: Motor overload protection
011: Inverter overload protection
012: Reserve
013: Power ON
014: Communication error
015: Output current detection(>F24)
Refer to F21 description:
C47 Remote keypad control selection
000: Disable
001: Enable. Operation according to F09 on signal loss.
002: Enable. Operation at the last set frequency on signal loss
.
(Stop mode by Inverter keypad or F04 parameter as appropriate).
1. Before Remote keypad installed, set C47 to 001 or 002 by main keypad, then POWER OFF
and install the Remote keypad.
2. When C47=001, C49~C53 set parameter disable the following parameters will be auto set:
Inverter communication address: No 1, Data bytes: 8 bit, Baud rated (bps): 38400, Parity bytes:
no parity, Stop bytes: 1 bit.
3. Set C47 to 000 by main keypad after Remote keypad removed.
4. C47 can’t be changed by Remote keypad.
Note: 1. For safety reason, please install or remove Remote keypad when POWER OFF.
2. If the Remote keypad installed while POWER ON and in stop mode, the inverter
will be controlled by Remote keypad.
3. If the Remote keypad installed while POWER ON and in run mode, the inverter
will be controlled by main keypad, it will not be effective until the inverter has
stopped.
C48 Copy module
000: Copy module Disabled
001: Copy to module from inverter (Read)
The display will be blinking with “CPy”
002: Copy to inverter from module (write)
The display will be blinking with “CPy”
003: Read/ write check (Compare the parameters)
The display will be blinking with “CPr”
Note: Module copy function is applicable only to inverters with the same voltage and KW
rating.
C49 set communication address, for the specific inverter when multi-inverters are controlled by
communication method.
C49 Inverter communication address: 001~ 254