Chapter 3 Environment description and installation
3-19
Control signal terminals block description
1 2 3 4 5 6 7 8 9 10 11 12
TM2
Symbol Description
RA
RB
Multi-functional output terminal
Normally open contact
Rated contact capacity:
(250VAC/
1A
)
(30VDC/1A)
Contact description: (refer to
parameter F21)
10V
Supply for external potentiometer for speed reference.
AIN
Analog frequency signal input terminal (high level : 8V/low level: 2V), adaptable
to PNP (refer to parameter F15 description)
24V
PNP (SOURCE) input, S1~S4 (S5/S6) common terminal, (set SW1 to PNP and
connect option card power.)
COM
NPN (SINK) input, S1~S4 (S5/S6) common terminal, (set SW1 to NPN, and
analog input, connect option card power, output signal common terminal.)
FM+
Multi-function analog terminal (refer to parameter F26 description),
output signal: DC 0-10V.
Symbol Description
S1
S2
S3
S4
Multi-function input terminals (refer to parameters F11~F14 description)
RA
RB
24V
S1
S2
S3
S4
COM
10V
AIN
COM
FM+
Figure 3-16 Signal terminal locations