Chapter 4 Software index
4-3
4.2
Parameter function list
Basic parameter function list
F
Function Description
Range/ Code
Factory
Default
Remarks
00
Inverter horse power
capacity
01 Acceleration time 1
00.1~999s
05.0
*1 *2
02 Deceleration time 1
00.1~999s
05.0
*1 *2
03 Motor rotation direction
000: Forward
001: Reverse
000 *1
04 Run command source
000: keypad
001: External Terminal
002: Communication Control
000
05 Frequency command source
000: UP/Down Key on control panel
001: Potentiometer on control panel
002: AIN input signal from (TM2)
003: Multi-function input terminal
UP/DOWN function
004: RS-485 Communication
frequency setting
000
06
External control operation
mode
000: Forward/ Stop-Reverse/Stop
001: Run/ Stop-Forward/Reverse
002:3-wire—Run/ Stop
000
07 Frequency upper limit
01.0 ~200Hz
50.0/60.0
*2
08 Frequency lower limit
00.0 ~200Hz
00.0
*2
09 Stopping method
000: Decelerate to stop
001: Coast to stop
000
10 Status display parameters
000: No display
001: Display
000 *1
11 Terminal S1 Function
000
12 Terminal S2 Function
001
13 Terminal S3 Function
005
14 Terminal S4 Function
006
15 Terminal AIN Function
000: Forward
001: Reverse
002: Preset Speed Command 1
003: Preset Speed Command 2
004: Preset Speed Command 3
005: Jog frequency Command
006: Emergency stop(E.S.)
007: Base Block (b.b.)
008: Select 2
nd
accel / decel time
009: Reset
010: Up command
011: Down command
012: Control signal switch
013: Communication control signal switch
014: Acceleration/deceleration prohibit
015: Master/Auxiliary speed source select
016: PID function disable
017: Analog frequency signal
input( terminal AIN)
018: PID feedback signal (terminal AIN)
019: DC Brake signal *6
020: DC Brake base on TM2 AIN
Frequency *9
017
16 AIN signal select
000: 0~10V(0~20mA)
001: 4~20mA(2~10V)
000
17 AIN Gain (%)
000~200
100
*1