Chapter 4 Software index
4-4
F
Function Description
Range/ Code
Factory
Default
Remarks
18 AIN Bias (%)
000~100
000
*1
19 AIN Bias
000: Positive
001: Negative
000 *1
20 AIN Slope Direction
000: Positive
001: Negative
000 *1
21 Multi-function output RY1
000: Run
001: Frequency reached
(Set frequency ± F23)
002: Frequency is within the range
set by (F22±F23)
003: Frequency Detection (>F22)
004: Frequency Detection (<F22)
005: Fault terminal
006: Auto reset and restart
007: Momentary power loss
008: Emergency Stop(E.S.)
009: Base Block (b.b.)
010: Motor overload protection
011: Inverter overload protection
012: retain
013: Power On
014: Communication error
015: Output current detection(>F24)
000
22
Output frequency at
the Set value (Hz)
00.0~200 00.0
*1
23
Frequency detection range
(±Hz)
00.0~30.0 00.0
*1
24 Output current set value
000~100%
000
25
Output current detection
time
00.0~25.5(Sec) 00.0
26
Multi-function output
analog type selection
(0~10Vdc)
000: Output frequency
001: Set frequency
002: Output voltage
003: DC voltage
004: Output current
005: PID feedback signal
000 *1
27
Multi-function analog
output gain (%)
000~200% 100
*1
28
Preset frequency 1 (Main
frequency setting)
00.0~200Hz 05.0
*1
29 Preset frequency 2
00.0~200Hz
05.0
*1
30 Preset frequency 3
00.0~200Hz
10.0
*1
31 Preset frequency 4
00.0~200Hz
20.0
*1
32 Preset frequency 5
00.0~200Hz
30.0
*1
33 Preset frequency 6
00.0~200Hz
40.0
*1
34 Preset frequency 7
00.0~200Hz
50.0
*1
35 Preset frequency 8
00.0~200Hz
60.0
*1
36 Jog frequency instruction
00.0~200Hz
05.0
*1