CT/L-14 Controller
5
4.2 Optional equipment
Power supply ................................................................................................................................ 1
PoE
-splitter
.................................................................................................................................. 1
Siren
............................................................................................................................................. 1
WRC kit
....................................................................................................................................... 2
AU05
system time display
............................................................................................................. 1
PERCo
readers
.................................................................................................................... up to 8
AC-02.1
interface converter
................................................................................................. up to 4
5 DESCRIPTION
5.1 Design and operation
The controller is produced in the form of electronics module in metal housing with a removable
cover. The cover features a power supply indication.
The controller features:
•
non-volatile memory;
•
non-volatile RTC-timer (real time clock);
•
housing opening sensor (the “tamper switch”).
The controller is able to store in non-volatile memory:
•
no less 50,000 card identifiers;
•
up to 150,000 events in the event log with the date and time of the event
.
The controller provides:
•
connection via Ethernet (
IEEE 802.3
) interface;
•
support of
TCP/IP
protocol suite
(ARP, IP, ICMP, TCP, UDP, DHCP)
;
•
support of application layer of communications protocol of
PERCo-Web
system;
•
updating of embedded software via
Ethernet
.
By default, the controller features:
•
unique MAC-address (specified in the certificate and on the item board);
•
IP-address (specified in the certificate and on the item board);
•
Subnet mask (255.0.0.0);
•
gateway IP-address (0.0.0.0).
Following ways to set up IP-address, gateway and subnet mask are provided at the stage of
system configuration:
•
operation with default settings;
•
manual input;
•
receipt from DHCP server.
It is possible to connect the following equipment:
•
up to eight readers via
RS-485
interface;
•
up to eight readers via
Wiegand
interface;
•
up to four door sensors (reed switches);
•
up to four passage sensors (PASS outputs of the turnstile);
•
up to four RC buttons (“Exit”) for the lock;
•
up to two turnstile (gate) RC-panels;
•
up to ten devices sending commands to additional inputs;
•
AU05
system time display;
•
Fire Alarm
emergency unlocking (emergency passage opening) device.
1
PoE-
splitter
– allows energizing the controller via
Ethernet
network. Splitter can be used with network
switches that support
PoE
technology and that are compatible with
IEEE 802.3af
standard.
2
WRC kit consists of a receiver and transmitters (fobs) with operating range of up to 40 m.
3
In case of event log overflow the oldest events will be replaced with the new ones (events are deleted by
blocks consisting of 256 events).