Operation Manual 

10 

“Relay contact” control element is to provide following signals characteristics: 

Minimum commutating current  ..................................................................................  max. 1 mA 

Closed contact resistance (with resistance of the connection cable)  ....................  max. 300 Ohm 

Circuit control element with open collector output is to provide following signals characteristics: 

Voltage at the closed contact (low-level signal at input of the controller)  ...................  max. 0.8 V 

5.4.2 

DUA

DUSt

DUB

FA

 inputs 

The controller provides status control of four inputs under control of “dry contact” or “open 

collector” (

OK

): 

DUA, DUSt, DUB, FA

. Connection to the inputs is performed via 

XT2

 and 

XT10 

terminal blocks of the controller lower board. 

 

Note: 

To create a high-level signal on all input contacts 

DUA, DUSt, DUB, FA, 

1 kOhm resistors 

connected to +3,3V power line are used. 

Inputs can be used for following connections: 

XT2 

terminal block: 

 

FA: 

emergency unlocking devices (passage opening) 

Fire Alarm, 

 

DUA:

 button “A” on the RC-panel #1 (WRC #1) or RC-button for OD1, 

 

DUSt: 

button “Stop” on the RC-panel #1 (WRC #1) or optional equipment (IN #8), 

 

DUB: 

button “B” on the RC-panel #1 (WRC #1) or RC-button for OD2 or optional equipment (IN #9). 

XT10 

terminal block: 

 

DUA: 

button “A” on the RC-panel #2 (WRC #2) or optional equipment (IN #10), 

 

DUSt: 

button “Stop” on the RC-panel #2 (WRC #2) or optional equipment (IN #11), 

 

DUB: 

button “B” on the RC-panel #2 (WRC #2) or optional equipment (IN #12). 

Activation and signals characteristics of the control element are specified in the Sect. 5.4.1. 

 

Notes: 

  Input 

FA

 is uniquely configured as “Closed”. 

  Input 

DUA

 is uniquely configured as “Opened”. 

  If according to the configuration of the controller input 

DUSt

 or 

DUB

 used to connect  

RC-buttons, it is uniquely configured as “Opened” without any possibility being 

modified. 

5.5  Output signals settings 

5.5.1 

OUT1

 – 

OUT4

 relay outputs 

The controller is equipped with four 

OUT1  –  OUT4 

relay outputs. Connection to the outputs is 

performed via 

XT6 – XT9

 terminal blocks of the controller lower board. Each output has a complex 

group of contacts: normally open 

NO

, normally closed 

NC

 and common output 

C

Outputs may be used for (Fig. 3)

 

OUT1:

 

as a control output of OD #1

 

OUT2, OUT3,

 

OUT4:

 

o

  as a control output of OD #2, OD #3 and OD #4,

 

o

  as outputs to control optional equipment (OUT #2

OUT #3

OUT #4).

 

Output signals characteristics: 

Maximum commutating voltage of direct current  ....................................................  max. 30 V 

Maximum commutating voltage of alternating current  ............................................  max. 42 V 

Maximum commutated direct/alternating current  ......................................................  max. 5 A 

Resistance of closed contact  .........................................................................  max. 0.15 Ohm 

Control outputs support potential and pulse operating  modes of OD. Selection of mode is 

performed with 

Operating

 

mode of control output

 parameter of OD

.

 

Содержание CT/L-14

Страница 1: ...Controller CT L 14 ASSEMBLY AND OPERATION MANUAL...

Страница 2: ...CT L 14 Controller Assembly Operation Manual...

Страница 3: ...13 8 2 Installation order 14 8 2 1 Controller installation 14 8 2 2 Door control configuration 16 8 2 3 Turnstile and electromechanical gates configuration 18 8 2 4 Vehicle checkpoint configuration 2...

Страница 4: ...thernet Appendix 4 p 2 and in browser address bar add the port number 49000 to controller IP address login password for initial entering admin admin After this Web server and system server are to be i...

Страница 5: ...ces RS 485 Wiegand1 Number of reading devices via RS 485 interface up to 8 via Wiegand2 interface up to 8 Number of users min 50 000 Event memory capacity up to 150 000 Number of access cards for each...

Страница 6: ...and on the item board IP address specified in the certificate and on the item board Subnet mask 255 0 0 0 gateway IP address 0 0 0 0 Following ways to set up IP address gateway and subnet mask are pro...

Страница 7: ...board process execution module The XS1 XS2 terminal blocks of the upper board are connected to the XP1 XP2 connectors of the lower board The controller boards are shown in Fig 1 The terminal blocks ap...

Страница 8: ...input IN 5 GND Common IN6 In 6 Additional input IN 6 XT2 RC1 connector FA FA Input for emergency unlocking passage opening Fire alarm GND Common DUA DUA 1 Control input of the OD1 from the RC button o...

Страница 9: ...r upper board Following ways of IP address setting are possible see Table 2 1 User mode Jumper is removed If the user does not change the IP address gateway subnet mask the controller operates with de...

Страница 10: ...t of a turnstile 2 o intrusion detectors of a vehicle checkpoint 2 o optional equipment IN 3 IN4 o door sensor 4 reed switch o PASS output of a turnstile 2 o optional equipment IN 4 IN5 IN6 o optional...

Страница 11: ...N 10 DUSt button Stop on the RC panel 2 WRC 2 or optional equipment IN 11 DUB button B on the RC panel 2 WRC 2 or optional equipment IN 12 Activation and signals characteristics of the control element...

Страница 12: ...notifications to central surveillance panel connection of other optional equipment Output signals characteristics Maximum commutation voltage of direct current max 30 V Maximum commutated current max...

Страница 13: ...03 interface converter up to four readers with the Wiegand interface can be connected to the controller and when using four AC 02 1 converters up to 8 readers can be connected The connection layout a...

Страница 14: ...Sect 7 1 Installation should be done in accordance with local building requirements 8 1 Cable lengths Cables for installation are shown in Table 3 Table 3 Cables used for installation N Equipment Cab...

Страница 15: ...ning on the controller s board is presented in Fig 1 Installation of connected devices turnstiles locks power supply etc is performed according to the instructions given in technical documents of corr...

Страница 16: ...n accordance with the Table 2 if necessary 6 Connect Ethernet cable to X2 connector of the controller upper board 7 Connect power source cable to XT4 terminal block of the controller lower board in ac...

Страница 17: ...mechanical electromagnetic locks Sect 8 2 2 turnstile Sect 8 2 3 vehicle checkpoint Sect 8 2 4 RC panel WRC Sect 8 2 5 emergency unlocking devices Fire Alarm Sect 8 2 6 other optional equipment Sect 8...

Страница 18: ...of the lock the latch to XT6 or XT9 terminal blocks on the lower board of the controller is performed in accordance with layout Fig 3 5 3 If connection of an Exit lock RC button is required connect it...

Страница 19: ...Operation Manual 18 8 2 3 Turnstile and electromechanical gates configuration Figure 6 Connection layouts of Turnstile control configuration...

Страница 20: ...iance with the layout Fig 6 3 Connect the turnstile the control unit of the turnstile to XT1 XT8 XT9 terminal blocks of the controller lower board in compliance with the layout Fig 6 4 Connect the swi...

Страница 21: ...hicle checkpoint OD are given in Fig 8 Notes Output normalization parameter of OD should be set into After closing mode If operation is performed via one relay Automatic closing function should be tur...

Страница 22: ...CT L 14 Controller 21 Figure 8 Connection layouts of boom barriers to the controller of vehicle checkpoint Figure 9 Connection layout of intrusion detectors...

Страница 23: ...assage opening of all ODs connected to the controller board and the controllers of the second level except ODs which are in Security operating mode the possibility of emergency unlocking is to be conf...

Страница 24: ...ional equipment with inductive load Rn to the outputs it is necessary to use spark protection diode VD1 in Fig 12 For example Schottky diode for operating current of min 1A 1N5819 Figure 11 Connection...

Страница 25: ...n Turn on the power source the LED indication is to light up on the controller housing It means that the controller is switched on 2 Connect to the controller Web interface via Ethernet network Append...

Страница 26: ...ler Web interface using computer via Ethernet Appendix 4 p 2 and in browser address bar add the port number 49000 to controller IP address login password for initial entering admin admin After this We...

Страница 27: ...ly transferred to the database on security system server Availability of verification function depends on installed extensions of network software 11 1 ACS operating modes The change of operating mode...

Страница 28: ...of the Fire Alarm input Any card 1 3 0 21 off off off No Open on off off off Control off on off off Security off 1 Hz 1 Hz off Closed off off on off Card is not authorized for access Open on off off 0...

Страница 29: ...Network settings in the computer are missing set IP address and subnet mask of the computer The controller should be connected either directly to network connector of network card of the computer or t...

Страница 30: ...aintenance and monitoring of the technical condition of means of the security fire alarm system Respecting of periodicity technological order and methods of execution of maintenance work are required...

Страница 31: ...troller by simulating the actuation of detectors in accordance with the resources configuration Indication on the controller corresponding to events is on Formation of signals at the outputs according...

Страница 32: ...CT L 14 Controller 31 APPENDICES Appendix 1 Instruction on connection of the card capture reader Figure 15 IC 05 card capture reader connection layout...

Страница 33: ...nfiguring the controller and the IC05 card capture reader is described in the Administrator s Guide of these systems and also in the IC05 Operation Manual An example of connection of the PERCo card ca...

Страница 34: ...nd of all the devices powered by it must not exceed 12 W It is also recommended to leave min 10 reserve power Splitter description PoE splitter hereinafter splitter is designed for energizing equipmen...

Страница 35: ...roller for lock chamber management Lock chamber is intermediate detached space passage through an OD which excludes a possibility of a pass through without additional verification visual identificatio...

Страница 36: ...egard to the lock chamber Reader can be replaced or duplicated by the RC button see below the lock chamber OD settings For comfort of use in the Web interface of the controller the lock chamber is pre...

Страница 37: ...r OD settings To operate the lock chamber passageway control sensors are activated PASS A and PASS B of turnstile 1 for direction of the passages 1 and 2 through OD1 PASS A and PASS B of turnstile 2 f...

Страница 38: ...3 5 Reading format of the card identifiers 40 4 CONFIGURATION 41 4 1 Controller configuration template 41 4 2 Configuration of the controller resources settings 42 4 2 1 Operating devices 42 4 2 2 Ph...

Страница 39: ...2 3 Make sure that the computer and the controller are on the same subnet Ethernet It may become necessary to change network settings of the computer browser settings and to check operation of the net...

Страница 40: ...g devices Physical contacts Readers Internal responses Events filters Access Time access criteria Time zones Holidays Weekly schedule Shift day Flexible weekly Users Operating device control Events St...

Страница 41: ...Server in the Web interface menu The page with working area will be opened 2 In the opened window make the necessary changes for the parameters Server address parameter sets the server address Encrypt...

Страница 42: ...be reset to the default template parameters The list of recorded access cards identifiers related user information access rights and parameters remain the same To change the configuration of the cont...

Страница 43: ...ill be opened 3 In the opened window on the Device management Security General access Access by direction tabs make the necessary changes of the settings for corresponding resources 4 Click the Save b...

Страница 44: ...e physical contact is attached to are to be set Inputs and outputs that are not involved in the template the value is Input Output These inputs and outputs are available for the task and changes in th...

Страница 45: ...e deleted 4 2 3 Readers In all controller configurations to each direction of every OD one reader or one infrared panel hereafter reader is assigned If necessary it is possible to add into the configu...

Страница 46: ...arameter sets line with Trassir server IP address Port parameter sets Trassir server port number Password parameter sets Trassir server authorization password Movement line parameter sets the number o...

Страница 47: ...se launch Response time and Response characteristics parameters set corresponding response settings 4 Click the Save button The Internal response window will be closed the changed settings will be pas...

Страница 48: ...l command Verification parameter sets the verification confirmation passage counter denial RC panel denial EVD denial Software denial verification timeout no response from passage counter no response...

Страница 49: ...t the Cancel button Also it is possible to close the window by clicking Close 6 To delete the time zone from the list click the title bar in the working area the Time zones window will be opened Selec...

Страница 50: ...from the list click the title bar in the working area the Holidays window will be opened Click the Delete button The Holidays window will be closed and the selected day will be deleted 5 1 3 Weekly sc...

Страница 51: ...lick the Add button to change or delete the Flexible daily schedule parameters click the title bar in the working area The Flexible daily schedule window will be opened 3 In the opened window perform...

Страница 52: ...r click the Save button The Flexible weekly schedule window will be closed 5 To exit the Flexible weekly schedule window without saving the changes select the Cancel button Also it is possible to clos...

Страница 53: ...ilarly if needed 5 Using the Fingerprints tab assign to the user the fingerprints For this purpose Click the Activate complement button and place the finger on the reader device To delete all the fing...

Страница 54: ...Note When arming the direction of the OD associated with the reader is set you select it in the dropdown Direction list When you unlock the OD will be unlocked for the time chosen in the drop down li...

Страница 55: ...ut state change Functioning Service 5 Use the Range beginning point and Range end point fields to set the period of the report 6 Click the Apply button to apply the filter click the Cancel button to c...

Страница 56: ...from Morpho click the Delete all fingerprints from Morpho button 4 To update the controller software firmware indicate the location of the software file using the Browse button and click the Download...

Страница 57: ...PERCo Polytechnicheskaya str 4 block 2 194021 Saint Petersburg Russia Tel 7 812 247 04 64 E mail export perco com support perco com www perco com...

Страница 58: ...www perco com...

Отзывы: