6. Push each of the fan boxes
F
in the direction of the air duct connections by approx. 3 - 4 mm so
that the heat exchanger box
G
is unlocked out of the tongue-and-groove joint.
Fig 49: Unlocking of the heat exchanger box
G
by shifting the fan boxes
F
In the event that the fan boxes F cannot be shifted, the air duct connection stubs of
the fan boxes F must be shortened!
Cut through the EPP connection stubs in the circumferential groove
H
(set point of sectioning)
Fig 50: Shortening of the EPP connection stub at the set point of sectioning of the circumferential
groove
H
After having finished the maintenance work, all disconnected air ducts must be
reconnected to the heat recovery unit in air-tight condition. A vapour resistant and
thermal insulation must be established at the sectioning points of the outside and
exhaust air connection stubs!