The values for the balancing factor are pre-set and should only be changed if needed.
Adjustment of the valves
3.5.3
Make sure that the supply and extract air valves are open as much as possible at the
beginning of the volume flow measurement.
•
Set the fans to nominal air volume flow.
•
Adjustment of the air volume flows to the air valves by means of a volume flow hood and an
anemometer (see air volume log)
•
Adjustment of the air gap on the valve must not be too narrow – aerodynamic noises! Better:
Adjustment of a lower fan output or restriction of the volume flow in the pipeline (installation of a
throttle flap or throttle foam insert)
•
Readjustment of the valves
•
Locking of the adjusted positions of the valves and flaps
•
Recording of the adjusted air quantity and all further adjustments in the designated documentations
Menu settings by qualified personnel / service staff
3.6
The password-protected parameters may only be changed by a competent expert or service
staff!
Main menu Setup
3.6.1
The main menu
Setup
is divided in eight submenus. The access to the submenus is password-protected.
Symbol
Designation
Explanation / actions
Button
Menu mode
By touching the button Menu mode, you reach the main menus.
Buttons
Navigation
By touching the navigation buttons, select the main menu setup
and confirm with Enter.
Button
Password
Password prompt
Enter the password _ _ _ _ _ and confirm with Enter.
Buttons
Navigation
By touching the navigation buttons, select the respective submenu
and confirm with Enter.
Tab. 30: Sequence of steps access main menu setup
The settings in the submenu are only applied if Enter is touched!
3.6.1.1 Submenu Frost protection
The following settings are made in the submenu Frost protection:
•
Parameterisation of the temperatures, () values factory setting:
o
Anti-freeze protection threshold intake air eco (-3.0 °C)
o
Anti-freeze protection threshold intake air safe (-2.0 °C)
o
Anti-freeze protection threshold intake air moisture heat exchanger (-3.0 °C)
o
Anti-freeze protection threshold minimum supply air temperature (5.0 °C)
Содержание CLIMOS F 200
Страница 1: ...Version 2 0_06 2016 EN...
Страница 57: ...57 Dimensional sketch 3 9 4 Fig 55 Dimension drawing HRU CLIMOS...
Страница 58: ...58 Circuit diagram CLIMOS Basic series 3 9 5 Fig 56 Terminal assignment CLIMOS Basic...
Страница 59: ...59 Circuit diagram CLIMOS Comfort series 3 9 6 Fig 57 Terminal assignment CLIMOS Comfort...
Страница 60: ...60 Terminal scheme master controller 3 9 7 Fig 58 Terminal assignment Master Controller...
Страница 65: ...65 Product fiche 4 5...