![Paul CLIMOS F 200 Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/paul/climos-f-200/climos-f-200_original-operating-instructions_4022625046.webp)
46
Button
Fan speed 3
(FS3)
Using the button Fan speed 3, activate the FS 3 and
parameterise it with the navigation buttons.
Setting range: FS2 < FS3 < 100 %
Using the b / -, an imbalance can be set.
Buttons
Enter
Cancel / back
Confirm by touching the Enter button. By touching the Cancel /
back button, exit the menu level.
Tab. 32: Parameterisation submenu fan speeds
3.6.1.3 Submenu
Post-heating
The following settings are made in the submenu supplementary heating:
•
Parameterisation of the duct temperature
•
Selection of the type of supplementary heater battery
o
Electric heater battery
o
Hot water heater battery
Symbol
Designation
Explanation / actions
Buttons
Navigation
Duct temperature
Select by touching the navigation buttons (red background of the
text) and confirm with Enter.
Buttons
+ / -
Using the b / -, set the duct temperature.
Buttons
Enter
Cancel / back
Confirm by touching the Enter button. By touching the Cancel /
back button, exit the menu level.
Buttons
Navigation
Selection Type supplementary heater battery
Select the respective type by touching the navigation buttons (red
background of the text).
Button
Checkmark
By touching the Checkmark button, the type of supplementary
heater battery is selected.
Button
Cancel / back
By touching the Cancel / back button, exit the menu levels until the
start menu appears.
Tab. 33: Parameterization submenu post-heating
3.6.1.4 Submenu Summer ventilation without by-pass
This menu shows whether summer ventilation without by-pass is possible. The menu can only be
executed, if there is no by-pass.
The following settings are made, () values factory settings
•
Temperature for activating the function (25.0 °C);
•
Hysteresis (0.5 °K)
•
Inactive below (13.0 °C)
Symbol
Designation
Explanation / actions
Button
Checkmark
The symbol shows the feasibility of the menu.
Содержание CLIMOS F 200
Страница 1: ...Version 2 0_06 2016 EN...
Страница 57: ...57 Dimensional sketch 3 9 4 Fig 55 Dimension drawing HRU CLIMOS...
Страница 58: ...58 Circuit diagram CLIMOS Basic series 3 9 5 Fig 56 Terminal assignment CLIMOS Basic...
Страница 59: ...59 Circuit diagram CLIMOS Comfort series 3 9 6 Fig 57 Terminal assignment CLIMOS Comfort...
Страница 60: ...60 Terminal scheme master controller 3 9 7 Fig 58 Terminal assignment Master Controller...
Страница 65: ...65 Product fiche 4 5...