A screened 4-wire cable is connected to the 5-pole screw terminal X1 of the adapter board. This cable
connects the adapter board to the 5-pole screw terminal of the control unit’s adapter board. In order to be
protected against error voltage, short circuit and dust, the adapter board must be mounted into the casing
made of transparent plastic. The cables connected to the adapter board must be placed into the cable
troughs of the casing and are fastened by means of the 3-fold click lock of the hinged cover. It is
recommended to use a cable of the type J-Y(ST)Y 2x2x0.6 LG internal cable with a colour coding
according to VDE0815 acc.Tab. 20.
Terminal X1 (adapter board / control unit)
Wire
Signal
X1.1 red
24P
X1.2 white
RX
X1.3 yellow
TX
X1.4 black
GND
X1.5 aluminium-coloured
screen
Tab. 20: Terminal assignment for terminal X1 adapter board and terminal X1 control unit
Connection of the TFT touch panel
3.4.2
The cable of the type J-Y(ST)Y 2x2x0.6 must be connected to the terminal X1 of the adapter board acc.
Tab. 20
The ribbon cable connects the adapter board to the board of the TFT touch panel.
Fig 28: Adapter board with terminal X1 on an in-wall base plate; ribbon cable of the adapter board;
board of the TFT touch panel (from left to right)
The connectors of the ribbon cable which are protected against polarity reversal must be
carefully plugged into the jacks of the respective boards!
Fig 29: Touchpad with stainless steel frame; ribbon cable of the control unit adapter; Touchpad engaged
in the in-wall base plate (from left to right)
The smaller side of the stainless steel frame of the ready-made TFT touch panel has to point upwards. In
doing so, the control unit adapter and the in-wall base plate have to be positioned in such a way that the
ribbon cable of the control unit adapter, which is arched downward, is plugged in the TFT-Touch panel.
The spring steel clips, which are mounted to the rear side of the control unit, grasp the in-wall base plate
and pull the stainless steel frame of the control unit tightly to the wall.
X1
Содержание CLIMOS F 200
Страница 1: ...Version 2 0_06 2016 EN...
Страница 57: ...57 Dimensional sketch 3 9 4 Fig 55 Dimension drawing HRU CLIMOS...
Страница 58: ...58 Circuit diagram CLIMOS Basic series 3 9 5 Fig 56 Terminal assignment CLIMOS Basic...
Страница 59: ...59 Circuit diagram CLIMOS Comfort series 3 9 6 Fig 57 Terminal assignment CLIMOS Comfort...
Страница 60: ...60 Terminal scheme master controller 3 9 7 Fig 58 Terminal assignment Master Controller...
Страница 65: ...65 Product fiche 4 5...