Fan speed (FS) Time slot (time 0
00
- 24
00
)
FS1
8
30
- 16
00
FS2
0
00
- 8
00
16
00
- 24
00
FS3
8
00
– 8
30
Tab. 9: Time slot factory setting, group weekdays Mon-Fri
Fig 8: Automatic timing factory setting, group weekdays Sat-Sun
Fan speed (FS)
Time slot (time 0
00
- 24
00
)
FS2
0
00
- 24
00
Tab. 10: Time slot factory setting, group weekdays San-Sun
The factory setting of the automatic timing can only be reactivated via the main menu
Setup.
If the operating mode “Automatic timing” is active in automatic mode, the active fan speed (FS 1-3 only)
is, in accordance with the time slot, visualised in grey on the start menu in addition to the icon Automatic
mode.
Fig 9: Automatic mode automatic timing with active fan speed FS2
2.3.2.4.2 Automatic
sensor
The operating mode
Automatic sensor
of the automatic mode requires the connection of an external air
quality / CO
2
or humidity sensor to the control of the ventilation device. The analogue signal of the sensor
is taken as control signal for the fan rotary speed of the ventilation device. When applying several sensors
in one ventilation plant, the output signal of a maximum value module is used for the control of the
ventilation device. At first, using the navigation buttons (red background of the text) and by setting the
checkmark, it is selected whether the sensor has a current output or voltage output (current: 4…20 mA,
voltage: 0…10 V), and this is confirmed with Enter. Subsequently, the lower point (range start parameter
p1) and the upper point (range stop parameter p2) of a linear characteristic curve for the fan speed are
Содержание CLIMOS F 200
Страница 1: ...Version 2 0_06 2016 EN...
Страница 57: ...57 Dimensional sketch 3 9 4 Fig 55 Dimension drawing HRU CLIMOS...
Страница 58: ...58 Circuit diagram CLIMOS Basic series 3 9 5 Fig 56 Terminal assignment CLIMOS Basic...
Страница 59: ...59 Circuit diagram CLIMOS Comfort series 3 9 6 Fig 57 Terminal assignment CLIMOS Comfort...
Страница 60: ...60 Terminal scheme master controller 3 9 7 Fig 58 Terminal assignment Master Controller...
Страница 65: ...65 Product fiche 4 5...