Error code 41: Occurrence condition of table setting error
● The last table of the positioning setting tables is not the E point. (e.g. The P point, C point
and J point are set continuously.)
● The control method of the J-point control table is absolute.
● The tables whose control method is absolute are set repeatedly.
● The opposite pulse output directions (forward/reverse) are set on the consecutive tables of P
+E points.
● Axes to which the interpolation operation setting is made are selected for the F383
simultaneous start instruction.
8.2.3 Motor Does Not Rotate/Move (Output LED Flashes or is ON)
■
Solution 1: For servo motor
Check to make sure the servo on input is set to “ON”.
■
Solution 2
Check to make sure the power supplies for the servo amplifier and motor driver are ON.
■
Solution 3
Check to make sure the servo amplifier and motor driver are connected to the unit correctly.
■
Solution 4
Check to make sure the settings for the pulse output method (CW/CCW method or Pulse/Sign
method) are appropriate.
8.2.4 Motor Does Not Rotate/Move (Output LED is OFF)
■
Solution
Review the program.
Point to check
● Check to make sure the I/O numbers are appropriate.
● Check non-rewriting of the start flag in the program.
● Check the input valid logic of the over limit switch. In this case, the error LED flashes.
8.2 What to Do If an Error Occurs
WUME-FPXHPOSG-01
8-7
Содержание FP-XH Series
Страница 2: ... MEMO 2 WUME FPXHPOSG 01 ...
Страница 18: ... MEMO 1 10 WUME FPXHPOSG 01 ...
Страница 30: ... MEMO 3 8 WUME FPXHPOSG 01 ...
Страница 51: ...4 4 Reading Elapsed Values WUME FPXHPOSG 01 4 21 ...
Страница 52: ... MEMO 4 22 WUME FPXHPOSG 01 ...
Страница 88: ... MEMO 5 36 WUME FPXHPOSG 01 ...
Страница 94: ... MEMO 6 6 WUME FPXHPOSG 01 ...
Страница 140: ... MEMO 9 8 WUME FPXHPOSG 01 ...
Страница 193: ... MEMO WUME FPXHPOSG 01 ...
Страница 194: ...Panasonic Industrial Devices SUNX Co Ltd 2020 October 2020 WUME FPXHPOSG 01 ...