● For the E-point control, enter settings in one row.
● For P-point, C-point and J-point controls, they should be combined with E-point control of the
next step as a pair and the setting should be input in two rows.
● When E: End point is not selected in the next row of P: Pass point, C: Continuance point or J:
Speed point, the self-diagnostic error (error code 44: positioning error) is detected.
■
Settings of J-point control
● For J-point control, only "Increment" can be selected as a control method.
● For changing speed during J-point control, set the target speed after the change in the
positioning parameter dialog box.
5.4.2 E-point Control (Single-Speed Positioning)
● The parameters for position control operations are specified in the positioning parameter
setting menus and data tables of Configurator PMX.
● When the positioning table start instruction (F380 POSST) or positioning simultaneous start
instruction (F383 MPOST) is executed, the pulse output will start and the positioning control
operation will be performed.
■
Operation diagram
t [ms]
f [Hz]
100ms
200ms
50ms
100,000 pulses
20,000Hz
1,000Hz
Instruction
start condition
Busy signal
Operation
done signal
Table 1
5.4 Positioning Control
WUME-FPXHPOSG-01
5-17
Содержание FP-XH Series
Страница 2: ... MEMO 2 WUME FPXHPOSG 01 ...
Страница 18: ... MEMO 1 10 WUME FPXHPOSG 01 ...
Страница 30: ... MEMO 3 8 WUME FPXHPOSG 01 ...
Страница 51: ...4 4 Reading Elapsed Values WUME FPXHPOSG 01 4 21 ...
Страница 52: ... MEMO 4 22 WUME FPXHPOSG 01 ...
Страница 88: ... MEMO 5 36 WUME FPXHPOSG 01 ...
Страница 94: ... MEMO 6 6 WUME FPXHPOSG 01 ...
Страница 140: ... MEMO 9 8 WUME FPXHPOSG 01 ...
Страница 193: ... MEMO WUME FPXHPOSG 01 ...
Страница 194: ...Panasonic Industrial Devices SUNX Co Ltd 2020 October 2020 WUME FPXHPOSG 01 ...