Operations of each contact
● The BUSY flags (X28 to X2D), which indicate that the motor is running, will turn ON when the
positioning control starts, and it will turn OFF when the operation completes.
● The operation done flags (X30 to X35), which indicate the completion of operation, will turn
ON when the current operation is completed, and they will be held until the next positioning
control, JOG operation or home return operation starts.
■
Settings
Item
Setting example
Axis setting area
Startup speed
1,000 Hz
Table area
Table number
Table 1
Table 2
Control method
Increment mode
Increment mode
Operation pattern
C-point control (Continuance
point control)
E-point control (End point
control)
Positioning
acceleration time
100 ms
150 ms
Positioning
deceleration time
200 ms
250 ms
Positioning target
speed
20,000 Hz
10,000 Hz
Positioning movement
amount
100,000 pulse
50,000 pulse
Dwell time
30 ms
50 ms
■
Configurator PMX settings
■
Sample program
The execution condition is differential execution. For details of instructions, refer to
5.4 Positioning Control
WUME-FPXHPOSG-01
5-21
Содержание FP-XH Series
Страница 2: ... MEMO 2 WUME FPXHPOSG 01 ...
Страница 18: ... MEMO 1 10 WUME FPXHPOSG 01 ...
Страница 30: ... MEMO 3 8 WUME FPXHPOSG 01 ...
Страница 51: ...4 4 Reading Elapsed Values WUME FPXHPOSG 01 4 21 ...
Страница 52: ... MEMO 4 22 WUME FPXHPOSG 01 ...
Страница 88: ... MEMO 5 36 WUME FPXHPOSG 01 ...
Страница 94: ... MEMO 6 6 WUME FPXHPOSG 01 ...
Страница 140: ... MEMO 9 8 WUME FPXHPOSG 01 ...
Страница 193: ... MEMO WUME FPXHPOSG 01 ...
Страница 194: ...Panasonic Industrial Devices SUNX Co Ltd 2020 October 2020 WUME FPXHPOSG 01 ...