Counting range of elapsed value (current value) area
Section
Range
High-speed counter
control
K–2,147,483,648 to K2,147,483,647
10.1.3 Areas Used For High-speed Counter Function
The usable combinations vary according to the unit type.
■
List of used areas
Channel
No.
Transistor output
type
Relay output type
Control
active
flag
Elapsed
value
area
Target value
area
Input no.
Input no.
Installation
position
Single-
phase
2-phase Single-
phase
2-phase
CH0
X0
X0, X1
X0
X0, X1
Control Unit
input
R9110
DT90300
DT90301
DT90302
DT90303
CH1
X1
-
X1
-
Control Unit
input
R9111
DT90304
DT90305
DT90306
DT90307
CH2
X2
X2, X3
X2
X2, X3
Control Unit
input
R9112
DT90308
DT90309
DT90310
DT90311
CH3
X3
-
X3
-
Control Unit
input
R9113
DT90312
DT90313
DT90314
DT90315
CH4
X4
X4, X5
X4
X4, X5
Control Unit
input
R9114
DT90316
DT90317
DT90318
DT90319
CH5
X5
-
X5
-
Control Unit
input
R9115
DT90320
DT90321
DT90322
DT90323
CH6
X6
X6, X7
X6
X6, X7
Control Unit
input
R9116
DT90324
DT90325
DT90326
DT90327
10.1 Overview of High-speed Counter Function
WUME-FPXHPOSG-01
10-3
Содержание FP-XH Series
Страница 2: ... MEMO 2 WUME FPXHPOSG 01 ...
Страница 18: ... MEMO 1 10 WUME FPXHPOSG 01 ...
Страница 30: ... MEMO 3 8 WUME FPXHPOSG 01 ...
Страница 51: ...4 4 Reading Elapsed Values WUME FPXHPOSG 01 4 21 ...
Страница 52: ... MEMO 4 22 WUME FPXHPOSG 01 ...
Страница 88: ... MEMO 5 36 WUME FPXHPOSG 01 ...
Страница 94: ... MEMO 6 6 WUME FPXHPOSG 01 ...
Страница 140: ... MEMO 9 8 WUME FPXHPOSG 01 ...
Страница 193: ... MEMO WUME FPXHPOSG 01 ...
Страница 194: ...Panasonic Industrial Devices SUNX Co Ltd 2020 October 2020 WUME FPXHPOSG 01 ...