Timing Chart (EtherNet/IP)
●
Control command execution
(1) The command code and command parameter are set from the Controller.
(2) The EXE input signal state is changed from OFF to ON. Execution is instructed to the displacement sensor.
(3) When the displacement sensor receives the execution instruction, the READY output signal turns OFF and
the command is executed.
(4) When the displacement sensor completes execution, the command code, response code and response
data are set.
(5) The FLG output signal turns ON.
(6) The Controller makes sure that the FLG output signal has turned ON, and then returns the EXE input signal
to OFF.
(7) The displacement sensor makes sure that the EXE input signal has turned OFF, and the FLG and READY
output signals automatically turn OFF and ON, respectively.
Command Code
Command
Parameter
EXE inp
u
t
Command Code
Response Code
Response Data
FLG o
u
tp
u
t
O
N
OFF
O
N
OFF
O
N
OFF
O
N
OFF
READY o
u
tp
u
t
O
N
OFF
O
N
OFF
O
N
OFF
O
N
OFF
(1)
(2)
(4)
(5) (6)
(3)
(7)
Command
Area
Response
Area
Содержание ZW-C1*AT
Страница 17: ...ZW User s Manual 1 15 ...
Страница 19: ...1 Basic configuration Basic configuration 1 1 ZW series Displacement Sensors 18 1 2 Basic Operation Flow 19 ...
Страница 54: ...Installing the Sysmac Studio 52 ZW User s Manual MEMO ...
Страница 74: ...Operating with Sensor Controller 72 ZW User s Manual MEMO ...
Страница 120: ...Setting the System 118 ZW User s Manual MEMO ...
Страница 138: ...Controll input signal with PC tool 136 ZW User s Manual MEMO ...
Страница 262: ...No protocol Connection 260 ZW User s Manual MEMO ...
Страница 270: ...Offline Debugging of the Sensor Control Program and Sensor Operation 268 ZW User s Manual MEMO ...
Страница 271: ...8 Troubleshooting Troubleshooting 8 1 Error Messages 270 8 2 Troubleshooting 284 ...
Страница 358: ...Connecting by No protocol Communications 356 ZW User s Manual MEMO ...
Страница 449: ......