Setting the Output Conditions
316
ZW User's Manual
Performing 2-point Scaling
Performing 2-point Scaling p.90
Operating procedure
Steps
Key operation
Display
Description
1 to 6
For moving to "SCALE" - "AUTO", see steps 1 to 6 in p.314.
7
Press the
/
keys to select "2PT" and press the
key.
8
Press the
key when the main display shows "POINT1".
9
Set the measured value of point 1.
The current measured value is displayed on the main display and the
current setting value is displayed on the sub-display.
To edit numerical values, use the
/
/
/
keys.
Enter the setting value and then press the
key.
10
Press the
key when the main display shows "POINT2".
11
Set the measured value of point 2.
To edit numerical values, use the
/
/
/
keys.
Enter the setting value and then press the
key.
12
"OK/CAN" is displayed on the sub-display.
Press the
key to execute scaling or
key to cancel.
13
Press the
key for two seconds to enter the RUN mode.
Содержание ZW-C1*AT
Страница 17: ...ZW User s Manual 1 15 ...
Страница 19: ...1 Basic configuration Basic configuration 1 1 ZW series Displacement Sensors 18 1 2 Basic Operation Flow 19 ...
Страница 54: ...Installing the Sysmac Studio 52 ZW User s Manual MEMO ...
Страница 74: ...Operating with Sensor Controller 72 ZW User s Manual MEMO ...
Страница 120: ...Setting the System 118 ZW User s Manual MEMO ...
Страница 138: ...Controll input signal with PC tool 136 ZW User s Manual MEMO ...
Страница 262: ...No protocol Connection 260 ZW User s Manual MEMO ...
Страница 270: ...Offline Debugging of the Sensor Control Program and Sensor Operation 268 ZW User s Manual MEMO ...
Страница 271: ...8 Troubleshooting Troubleshooting 8 1 Error Messages 270 8 2 Troubleshooting 284 ...
Страница 358: ...Connecting by No protocol Communications 356 ZW User s Manual MEMO ...
Страница 449: ......