User’s Manual
Section 3
Setting Output Processing of Sensing Information
■
Setting Two-point Scaling
Measurement is performed at two positions and offset values are set for those mea-
surements.
Example:
Correcting display values to match actual distances
Separate the two specified points by at least 1% of the rated measurement range for the connected
Sensor Head.
Example: For the ZS-LD80 (diffuse reflection type)
The two measured points must be separated by at least “30 mm x 0.01 = 0.3 mm” as the
measuring range is “30 mm ± 15 mm”.
FUN Mode-[OUTPUT]-[SCALING]-[ON]-[AUTO]
1.
Set the first point by following steps 1 to 4 of the
one-point scaling procedure.
80
78
68
67
67
80
Display value
(mm)
Actual
measured
value
(mm)
Sensor Head
Actual distance:80 mm
Display value:78 mm
Sensing
object
Sensing
object
Sensor Head
Actual distance:67 mm
Display value:68 mm
INPUT POINT 1
VAL SET:OK
DIG