User’s Manual
Section 4
Linear Input/Output
Non-Measurement Settings
Set how the measurement values are to be output when a non-measurement state occurs
temporarily due to insufficient received light amount or the reset input state, for example.
Example: When the waveform skips due to insufficient received light amount
FUN mode -[I/O SET]-[NON-MEAS]
In hold measurement, the output before the first hold value is obtained will be the same as [CLAMP]
even if [KEEP] is set.
ONE
SHOT
When the judgment result changes to
PASS, outputs the PASS output for the
time set to the timer.
Neither the HIGH nor the LOW output
is output.
Range: 1 to 5000 (ms)
Setting
Outputs
Judgment output
Linear output
KEEP
The status immediately before measurement is stopped is held and output.
CLAMP
(default
value)
All OFF
Outputs the set CLAMP value.
At current output : 4, 12 mA, 20 mA, MAX (approx. 25 mA, default value),
MIN (approx. 2 mA)
At voltage output : -10V, 0V, 10V, MAX (approx. 11 V, default value),
MIN (approx. -11 V)
Setting
Description
ON
OFF
ON
OFF
ON
OFF
Measured value
HIGH threshold value
LOW threshold value
HIGH output
PASS output
LOW output
: Timer time
Direction of
workpiece
movement
Amount of displacement
Amount of displacement
State with waveform skip caused
by insufficient light amount
As the value before the skip occurred is kept,
this is effective in canceling waveform skip.
When [KEEP] is selected
Содержание ZS-L -
Страница 1: ...USER S MANUAL Smart Sensor ZS L Series Ver 2 0 Cat No Z208 E1 02 ...
Страница 52: ...2 24 Section 2 INSTALLATION CONNECTION ZS L User s Manual Section 2 SmartMonitor ZS ...
Страница 90: ...3 38 Section 3 SETUP ZS L User s Manual Section 3 Setting the System Environment MEMO ...
Страница 156: ...6 46 Section 6 APPENDIX ZS L User s Manual Section 6 INDEX ...
Страница 158: ......