245
Timer and Counter Instructions
Section 3-6
2.
It is not possible to read the timer PVs of TIMU(541), TIMUX(556),
TMUH(544), and TMUHX(557).
3-6-1
HUNDRED-MS TIMER: TIM/TIMX(550)
Purpose
TIM or TIMX(550) operates a decrementing timer with units of 0.1-s. The set-
ting range for the set value (SV) is 0 to 999.9 s for TIM and 0 to 6,553.5 s for
TIMX(550). The timer accuracy is 0 to 0.01 s.
Note The timer accuracy for CS1D CPU Units is 10 ms + the cycle time. The timer
accuracy for unit version 4.1 of the CJ1-H-R CPU Units is
−
0.1 to 0 s. The
timer accuracy for other unit versions of the CJ1-H-R CPU Units is 0 to 0.01 s.
Ladder Symbol
Variations
Applicable Program Areas
Operands
N: Timer Number
The timer number must be between 0000 and 4095 (decimal).
S: Set Value
The set value must be between #0000 and 9999 (BCD).
(If the set value is set to #0000, the Completion Flag will be turned ON when
TIM/TIMX(550) is executed.)
Operand Specifications
PV
refresh
method
Symbol
Operands
BCD
N: 0000 to 4095 (decimal)
S: #0000 to #9999 (BCD)
Binary
N: 00000 to 4095 (decimal)
S: &0 to &65535 (decimal)
#0000 to #FFFF (hex)
TIM
N
S
N
: Timer number
S
: Set value
TIMX(550)
N
S
N: Timer number
S: Set value
Variations
Executed Each Cycle for ON Condition
TIM/TIMX(550)
Executed Once for Upward Differentiation
Not supported.
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program areas
Step program areas
Subroutines
Interrupt tasks
Not allowed
OK
OK
Not allowed
Area
N
S
CIO Area
---
CIO 0000 to CIO 6143
Work Area
---
W000 to W511
Holding Bit Area
---
H000 to H511
Auxiliary Bit Area
---
A000 to A959
Timer Area
0000 to 4095 (decimal)
T0000 to T4095
Counter Area
---
C0000 to C4095
DM Area
---
D00000 to D32767
Содержание SYSMAC CS Series
Страница 2: ......
Страница 4: ...iv ...
Страница 30: ...xxx ...
Страница 186: ...146 List of Instructions by Function Code Section 2 4 ...
Страница 194: ...154 3 35 4 MOVE BIT MOVBC 568 1273 3 35 5 BIT COUNTER BCNTC 621 1275 3 35 6 GET VARIABLE ID GETID 286 1277 ...
Страница 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Страница 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Страница 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Страница 1392: ...1352 ASCII Code Table Appendix A ...
Страница 1404: ...1364 Revision History ...