1145
Failure Diagnosis Instructions
Section 3-30
The following screen capture shows the PLC Setup setting from the CX-Pro-
grammer.
The following table shows the PLC Setup setting from the Programming Con-
sole.
Even if PLC Setup word 129 bit 15 is set to 1 (Do not record FAL Errors in
Error Log.), the following errors will be recorded:
• Fatal errors generated by FALS(007)
• Non-fatal errors from the system
• Fatal errors from the system
• Non-fatal errors from the system generated intentionally with FAL(006) or
FPD(269)
• Fatal errors from the system generated intentionally with FALS(007)
Clearing Non-fatal Errors without a Programming Device
1.
Clearing User-defined Non-fatal Errors
When FAL(006) is executed with N set to 0, non-fatal errors can be cleared.
The value of S will determine the processing, as shown in the following ta-
ble.
2.
Clearing Non-fatal System Errors (CS1-H, CJ1-H, CJ1M, and CS1D CPU
Units Only)
There are two ways to clear non-fatal system errors generated with
FAL(006).
• Turn the PLC OFF and then ON again.
Item
Setting
Programming Console
setting address
Word
129
Bit
15
Name
FAL Error Log Registration
Settings
0: Record FAL Errors in Error Log.
1: Do not record FAL Errors in Error Log.
Default setting
0: Record FAL Errors in Error Log.
Times that PLC Setup set-
ting is read
Every cycle (when an FAL Error occurs)
S
Process
&1 to &511 (0001 to 01FF hex) The FAL error of the specified number will be
cleared.
FFFF hex
All non-fatal errors (including system errors) will
be cleared.
0200 to FFFE hex or word
specification
T
he most serious non-fatal error (even if it is a
non-fatal system error) that has occurred.
When more than one FAL error has occurred,
the FAL error with the smallest FAL number will
be cleared.
Содержание SYSMAC CS Series
Страница 2: ......
Страница 4: ...iv ...
Страница 30: ...xxx ...
Страница 186: ...146 List of Instructions by Function Code Section 2 4 ...
Страница 194: ...154 3 35 4 MOVE BIT MOVBC 568 1273 3 35 5 BIT COUNTER BCNTC 621 1275 3 35 6 GET VARIABLE ID GETID 286 1277 ...
Страница 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Страница 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Страница 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Страница 1392: ...1352 ASCII Code Table Appendix A ...
Страница 1404: ...1364 Revision History ...