192
Sequence Output Instructions
Section 3-4
the input device) can cause the operand bit of KEEP(011) to be reset. This sit-
uation is shown below.
The operands for KEEP(011) are input in a different order in ladder diagrams
and mnemonic code.
Ladder diagram order: Set input
→
KEEP(011)
→
Reset input
Mnemonic code order: Set input
→
Reset input
→
KEEP(011)
Example
When CIO 000000 goes ON in the following example, CIO 00500 is turned
ON. CIO 00500 remains ON until CIO 000001 goes ON.
When CIO 000002 goes ON and CIO 000003 goes OFF in the following
example, CIO 00100 is turned ON. CIO 00100 remains ON until CIO 000004
or CIO 000005 goes ON.
Coding
Note KEEP(011) is input in different orders on in ladder and mnemonic form. In lad-
der form, input the set input, KEEP(011), and then the reset input. In mne-
monic form, input the set input, the reset input, and then KEEP(011).
NEVER
S
R
A
KEEP
120000
A
Input Unit
Address
Instruction
Operand
000100
LD
000000
000101
LD
000001
000102
KEEP (011)
000500
000103
LD
000002
000104
AND NOT
000003
000105
LD
000004
000106
OR
000005
000107
KEEP (011)
000100
Содержание SYSMAC CS Series
Страница 2: ......
Страница 4: ...iv ...
Страница 30: ...xxx ...
Страница 186: ...146 List of Instructions by Function Code Section 2 4 ...
Страница 194: ...154 3 35 4 MOVE BIT MOVBC 568 1273 3 35 5 BIT COUNTER BCNTC 621 1275 3 35 6 GET VARIABLE ID GETID 286 1277 ...
Страница 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Страница 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Страница 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Страница 1392: ...1352 ASCII Code Table Appendix A ...
Страница 1404: ...1364 Revision History ...