Internal CW/CCW Limits
You can also make settings in the DM area to place internal limits on rotation
of the axis on both the CW and CCW sides of the origin.
CCW
Internally set value of CCW limit
0
Internally set value of CW limit
CW
Positioning axis
DM words m+6 through m+5, 7 digits
Set to between 1 and 8388606.
DM words m+8 through m+7, 7 digits
Set to between 1 and 8388607.
The following values will be automatically set if the internal limit settings are
0.
CW:
8388607
CCW:
8388608
Operation
START (Positioning Actions)
If either of these limits is reached during execution of positioning actions,
pulse output will stop and an error code, either 5030 or 5031, will be gener-
ated.
Manual Operation
If either of these limits is reached during execution of LOW-SPEED JOG,
HIGH-SPEED JOG, or INCH, pulse output will stop and an error code, either
5070 or 5071, will be generated.
3–7–4
Data Calculations
Slight differences exist between speeds set in the DM area and actual
speeds. These differences do not affect positioning accuracy.