![Omron SYSMAC C200H-NC112 Скачать руководство пользователя страница 102](http://html1.mh-extra.com/html/omron/sysmac-c200h-nc112/sysmac-c200h-nc112_operation-manual_742431102.webp)
94
Present
position
DM 1052
DM 1053
DM 1054
CCW
positioning axis
0
CW
Data set using TEACH is valid immediately and can be used for positioning
actions without turning off the power or transferring data. Note that data re-
written using the Programming Console is not valid until data has been trans-
ferred again.
4–8–1
IR Area Settings
In C200H PCs, IR words 100 to 199 are used for Special I/O Units. When a
Position Control Unit is used, they are allocated as I/O refresh areas. For a
detailed explanation, see
Section 3–4. For a detailed table of words and bits
in the IR area, see
Appendix D.
When the No-origin flag is OFF and pulse output is stopped at the position to
be taught, the present position is set in IR words n+8 and n+9.
IR word n+1, bits 15 to 08
Set an integer between 00 and 19. The number set here indicates the posi-
tioning action for which the present position is to be set as the target position.
IR word n, bit 09
TEACH is executed when this bit is ON.
4–8–2
Execution Example
1
0
1
0
1
0
TEACH positioning action no.
IR n+1, bits 15 to 08
TEACH
IR n, bit 09
Teaching completed flag
IR n+5, bit 09
Busy flag
IR n+5, bit 12
4–8–3
Teaching From the Programming Console
This example display shows how to teach positions from the Programming
Console for Unit #0. It assumes that ORIGIN SEARCH has been executed,
Present Position
TEACH Positioning Action
Number
TEACH Command Bit
TEACH