Appendix G
Using the C200H-NC112 with CS1-series PCs
166
Allocated DM Area
(m = unit number
×
100)
Bit
m
to
m+20
m+22
to
m+81
m+82
to
m+99
Parameters
Position data
Speed and acceleration/
deceleration data
15
0
Contents
Direction
Initial positioning action number,
initial speed number, backlash
compensation
Positioning actions #0 to #19
Speeds #0 to #15, acceleration
data, deceleration data
CPU Unit
→
PCU
CPU Unit
→
PCU
CPU Unit
→
PCU
Setup Procedure
Initial Hardware Settings
1, 2, 3... 1.
Set the unit number and the operation mode using the rotary switches on the front of the
PCU.
2.
Mount to a CS1 CPU Rack, a C200H I/O Expansion Rack, a CS1 Expansion Rack, or a SYS-
MAC BUS Remote I/O Slave Rack. For basic systems, up to 10 PCUs can be mounted.
(There are no restrictions on the mounting position.)
3.
Connect the external I/O connectors for each of the axes.
4.
Connect the Programming Device.
5.
Turn ON power to the PC.
6.
Create the I/O table.
Initial Software Settings
1, 2, 3... 1.
Make the settings for parameters and position, speed, acceleration, and deceleration data in
the allocated DM Area.
2.
Reset the power, or turn the Unit Restart flag from OFF to ON.
Transferring Data
Use the TRANSFER DATA command to send data in the case where the above settings for position, speed, accel-
eration, and deceleration data are insufficient, or to change initial settings for this data.
1, 2, 3... 1.
When the TRANSFER DATA command bit (word n, bit 10) is turned from OFF to ON, the data
at the address in I/O memory specified with words n+3 and n+4 in the CIO Area is transferred
to the address (transfer number) in the PCU specified with bits 08 to 14 in word n+2 in the
CIO Area.
Starting Operation
1, 2, 3... 1.
Set the initial positioning action number (word n+1, bits 00 to 07) using MOV or another
instruction.
2.
Turn the START command bit (word n, bit 00) from OFF to ON using OUT or another instruc-
tion.
Programming
Set positioning data (initial data) in the allocated DM Area, and start operation. To do this, with the Busy flag (word
n+5, bit 12) as an N. C. input condition, turn the START command bit and the valid initial positioning number bit
from OFF to ON using OUT or another instruction.
Transferring Additional Data
1, 2, 3... 1.
With the Busy flag (word n+5, bit 12) as an N. C. input condition, set the transfer data (words
n+2 to n+4) using the MOV instruction.