
19
ORIGIN SEARCH
Origin proximity signal
Z-phase signal
Pulse output
Deviation counter reset output
Busy flag
Approx. 30 ms
Time
In this example, the mode switch is set to 2 and the DIP switch pins are set
as follows:
1
OFF
CW/CCW output
2
ON
Origin search direction: CCW
3
ON
Origin proximity present
4
ON
Origin proximity signal from NO input (rising edge)
5
ON
Origin signal from NO input (rising edge)
6
Refer to
Section 4–10 External Interrupt Commands.
7
8
ON
Origin proximity reverse present (rising, falling edge)
Origin search is started after the origin proximity signal has risen and fallen,
and stops with completion of the first Z-phase signal after deceleration has
stopped.
Example 3:
Settings in Mode 2
Switch Settings