Error Code List
Appendix F
162
Error
ORIGIN RETURN
disabled
HIGH-SPEED
JOG disabled
LOW-SPEED JOG
disabled
INCH disabled
Emergency stop
executed
CW limit
CCW limit
No origin proximity
signal
Error code
5200
5300
5400
5500
6000
6100
6101
6200
Problem
ORIGIN RETURN cannot be executed
because of data for ORIGIN RETURN
speed or backlash compensation that
generated alarm.
HIGH-SPEED JOG cannot be executed
because of data for HIGH-SPEED JOG
speed, initial speed, acceleration, deceler-
ation, or backlash compensation that gen-
erated an alarm.
LOW-SPEED JOG cannot be executed
because of data for LOW-SPEED JOG
speed, initial speed, or backlash compen-
sation that generated an alarm.
INCH cannot be executed because of
data for backlash compensation that gen-
erated an alarm.
Feeding has been stopped by emergency
stop signal input.
Feeding has been stopped by CW limit
signal input.
Feeding has been stopped by CCW limit
signal input.
No proximity signal is detected between
the CCW and CW limits even though pin
#3 on DIP switch designates a proximity
signal.
No-origin flag
Origin signal
position
Counterclockwise
CW limit
Clockwise CCW
limit
PC mode change
Correction
Based on error code, read out alarm
code and correct and correct data
accordingly. After transferring data,
the error code will be erased for the
next operation if data has been prop-
erly corrected. For data that cannot
be transferred, restart after correct-
ing DM.
Check wiring.Turn off emergency
stop signal and execute RELEASE
PROHIBIT and ORIGIN SEARCH.
Check wiring. Execute RELEASE
PROHIBIT and then feed counter-
clockwise using JOG, or INCH (or
execute ORIGIN SEARCH, Present
Position Reset, or TRANSFER DATA
after RELEASE PROHIBIT).
Check wiring. Execute RELEASE
PROHIBIT and then feed clockwise
using HIGH-SPEED JOG,
LOW-SPEED JOG, or INCH (or ex-
ecute ORIGIN SEARCH after RE-
LEASE PROHIBIT).
Check DIP switch setting, wiring of
proximity signal, and signal type (NC
or NO).
6201
6202
6400
6401
6600
The origin signal is not detected between
CCW and CW limits.
Feeding was stopped by origin signal in-
put during ORIGIN SEARCH before the
proximity speed was reached, i.e., prox-
imity signal and origin signal are too
close relative to time required for decel-
eration from high speed to proximity
speed
CW limit signal was input while feeding
counterclockwise.
CCW limit signal was input while feeding
clockwise.
PC mode was changed between MONI-
TOR and PROGRAM during pulse out-
put.
Check wiring of origin signal and
signal type (NC or NO)
Check position of origin signal and
proximity signal relative to required
deceleration.
Check wiring of limit signals.
Check wiring of limit signals.
Execute ORIGIN SEARCH to obtain
present position.