Troubleshooting Tables
Section 9-3
CPU Errors Resulting in Customizable Counter Unit Fatal Errors
No END
Lit
OFF
Lit
OFF
NO END
INST
0360 Hex
00 Hex
F0 Hex
F0 Hex
SR
23511
END(01) is not written anywhere in
program.
Write END(01) at the final address
of the program.
Unit sys-
tem error
(FALS)
Lit
OFF
Lit
OFF
SYS FAIL
FALS**
0360 Hex
00 Hex
FALS No. (1
to 99 BCD)
FALS No.
(1 to 99
BCD)
SR
23511
An FALS(07) instruction has been
executed in the program.
Check the FALS number to deter-
mine the conditions that would
cause execution, correct the cause,
and clear the error.
Unit cycle
time moni-
tor error
Lit
OFF
Lit
OFF
SYS FAIL
FALS9F
0360 Hex
00 Hex
F9 Hex
F9 Hex
SR
23511
The cycle time has exceeded the
FALS 9F Cycle Time Monitoring
Time (DM 6618).
Check the cycle time and adjust the
Cycle Time Monitoring Time if nec-
essary.
Error
Unit indicators
Error
message
Error log
(SIOU code,
details 1,
details 2)
SR 23500
to
SR 23507
Error
flags
Meaning and corrective
measures
RUN OPN
ERC
ERH
Unit recog-
nition error
OFF
OFF
Lit
Lit
---
---
---
---
The Customizable Counter Unit is
not recognized as a Special I/O Unit
by the CPU Unit.
Try to power-on again.
Unit not
recognized
OFF
OFF
OFF
Lit
---
0006 Hex
08 Hex
00 Hex
---
---
The actual I/O tables do not agree
with the registered I/O tables.
Recreate the I/O tables in the CPU
Unit.
Unit num-
ber error
OFF
OFF
OFF
Lit
---
---
---
---
The unit number is not set correctly
or the same number has been set
for another Unit.
Correct the unit numbers and try to
power-on again.
Unit set-
ting read
error
OFF
OFF
OFF
Lit
---
---
---
---
No response to a FINS command or
CPU settings could not be read.
Try to power-on again.
Bus error
OFF
OFF
OFF
Lit
---
---
---
---
The access right could not be
obtained.
Try to power-on again.
Error
Unit indicators
Error
message
Error log
(SIOU code,
details 1,
details 2)
SR 23500
to
SR 23507
Error
flags
Meaning and corrective
measures
RUN OPN
ERC
ERH
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......